General
The Modular Power Supply SPD is made from special non-metallic materials by using the stack discharge technology. It is used in primary power distribution systems to protect installations against direct lightning strikes and induced surges.
Features
High discharge capacity, low residual voltage, and high follow current extinguishing capability.
Standard guide rail installation.
Failure indication and remote signalling alarm interface for faults.
Standards Complied
IEC 61643-11:2011 Low-voltage surge protective devices - Part 11 Surge protective devices connected to low-voltage power systems –Requirements and test methods
EN 61643-11:2012 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems -Requirements and test methods
Technical Data
Operating Environment
Temperature range –40°C to +85°C
Relative humidity range 5% to 95% (+25°C)
Altitude range –500 m to +3000 m
Technical Parameters
Model ZGGF50-385(3+1)AYc ZGGF50-385(4+0)AYc ZGGF50-385(3+0)AYc ZGGF50-385(1+1)AYc ZGGF50-385(2+0)AYc
SPD according to IEC 61643-11 Class Ⅰ+ Class Ⅱ
SPD according to EN 61643-11 Type 1+Type 2
Number of ports (connection mode) One port ( in parallel)
Nominal operating voltage U o 230 V 50/60 Hz
Max. continuous operating voltage U C 385 V(L-N), 255 V(N-PE) 50/60 Hz 385 V(L-PE, N-PE) 50/60 Hz 385 V(L-PE) 50/60 Hz 385 V(L-N), 255 V(N-PE) 50/60 Hz 385 V(L-PE, N-PE) 50/60 Hz
Type of LV systems TN TN-S TN-C TN-S TN
Modes of protection L-N, N-PE L-PE, N-PE L-PE L-N, N-PE L-PE, N-PE
Nominal discharge current I n (8/20 μs) 50 kA (L-N), 100 kA (N-PE) 50 kA (L-PE, N-PE) 50 kA (L-PE) 50 kA (L-N), 100 kA (N-PE) 50 kA (L-PE, N-PE)
Impulse discharge current I imp (10/350 μs) 50 kA (L-N), 100 kA (N-PE) 50 kA (L-PE, N-PE) 50 kA (L-PE) 50 kA (L-N), 100 kA (N-PE) 50 kA (L-PE, N-PE)
Quantity of electric charge Q 25 As (L-N), 50 As (N-PE) 25 As (L-PE, N-PE) 25 As (L-PE) 25 As (L-N), 50 As (N-PE) 25 As (L-PE, N-PE)
Specific energy W/R 625 kJ/Ω (L-N), 2500 kJ/Ω (N-PE) 625 kJ/Ω (L-PE, N-PE) 625 kJ/Ω (L-PE) 625 kJ/Ω (L-N), 2500 kJ/Ω (N-PE) 625 kJ/Ω (L-PE, N-PE)
Measured limiting voltage U L ( at I imp ) ≤0.8 kV (after 10 μs, L-N)
≤1.0 kV (after 10 μs, N-PE)
≤0.8 kV (after 10 μs, L-PE, N-PE) ≤0.8 kV (after 10 μs, L-PE) ≤0.8 kV (after 10 μs, L-N)
≤1.0 kV (after 10 μs, N-PE)
≤0.8 kV (after 10 μs, L-PE, N-PE)
Voltage protection level U p 2.5 kV (L-N), 2 kV (N-PE) 2.5 kV (L-PE, N-PE) 2.5 kV (L-PE) 2.5 kV (L-N), 2 kV (N-PE) 2.5 kV (L-PE, N-PE)
Expected short circuit current of power supply I p 2 kA
Follow current interrupt rating(peak) I f i 2 kA (at 385 V a.c.) (L-N)
0.1 kA (at 255 V a.c.) (N-PE)
2 kA (at 385 V a.c.) (L-PE, N-PE) 2 kA (at 385 V a.c.) (L-PE) 2 kA (at 385 V a.c.) (L-N)
0.1 kA (at 255 V a.c.) (N-PE)
2 kA (at 385 V a.c.) (L-PE, N-PE)
Response time t A ≤100 ns (L-N, N-PE) ≤100 ns (L-PE, N-PE) ≤100 ns (L-PE) ≤100 ns (L-N, N-PE) ≤100 ns (L-PE, N-PE)
Leakage current ≤3 mA (L-N) ≤3 mA ( L-PE, N-PE ) ≤3 mA (L-PE) ≤3 mA (L-N) ≤3 mA ( L-PE, N-PE )
Residual current I PE ≤3 mA
Ratings and characteristics for external disconnector 500 A gL/gG
Installation location Indoor
Degree of protection IP 20 (after installation)
Method of mounting 35 mm DIN rail
Indication of disconnector operation Green: OK; Off: Replace
Cross-sectional area Stranded: 6 mm 2 to 25 mm 2
Torque: connecting terminal/Remote signalling interface 2.5 Nm/0.25 Nm
Remote signalling parameters Max. : 250V/0.1A ( a.c.) , min. : 12V/1mA ( a.c.)
Max. : 30V/0.1A ( d.c.) , min. : 12V/1mA ( d.c.)
Cross-sectional area for remote signalling terminals 0.15 mm 2 ~1.3 mm 2
Material of enclosure PC
Flammability UL94 V0
Storage period 2 years
Guarantee period 2 years
Circuit Diagram
ZGGF50-385(3+1)AYc
ZGGF50-385(4+0)AYc
ZGGF50-385(3+0)AYc
ZGGF50-385(1+1)AYc
ZGGF50-385(2+0)AYc
Configuration
ZGGF50-385(3+1)AYc
ZGGF50-385(4+0)AYc
ZGGF50-385(3+0)AYc
ZGGF50-385(1+1)AYc
ZGGF50-385(2+0)AYc